BCSE=Capacity Rapid Analysis Function + Cell Voltage Monitoring Function + Constant Current Discharge Function
I. Main Functions of Intelligent Battery Bank Load Tester
1. The product simultaneously has three functions: capacity analysis, cell voltage monitoring, and constant current discharge.
2. Constant current discharge current: For UPS battery bank 600V system, 0-30A continuously adjustable, single unit can meet the maintenance test of up to 300AH UPS batteries.
3. Number of batteries monitored simultaneously: 1 to 36 cells. Operation is simpler.
4. Has full deep discharge function: can meet ten hours of continuous discharge, accurately measure battery capacity.
5. Has rapid capacity analysis function: can estimate remaining battery capacity through a five-minute discharge.
6. Has parallel operation function: two units can be used in parallel for constant current discharge simultaneously, and after parallel operation, it can meet the maintenance test of 600AH batteries.
7. Has float charge period recording function: can record battery status during float charge period and timely propose suggestions for "equalizing charge" when necessary.
Intelligent Battery Bank Load Tester
Over the past twenty years, Taiwan Qunling's iron lithium battery charge and discharge testing equipment solutions have won widespread recognition and good reputation among users. It is the weather vane of power maintenance testing in China and a leader in the field of lithium iron phosphate battery detection, maintenance, and management. Products are sold nationwide in industries such as electric power, power plants, mobile, communications, railways, petrochemicals, military, education, scientific research, and environmental protection. We are now recruiting agents and providing technical and product support! Welcome to inquire!