全自动Dielectric Loss Tester-扬州达瑞

SF6 Intelligent Micro-Water Dew Point Meter

Published: 2019-10-03 16:28:48

Views: 2922

Category: SF6 Smart Micro-Water Meter

Product Description


SF6 Intelligent Micro-Water Dew Point Meter



Features



Automatic zero calibration



Advanced probe protection function



Full-range curve tracking and correction



Simple operation and easy portability



Unique large-screen display



Anti-pollution and anti-interference



Exclusive large storage capacity



Good repeatability and fast response



*Curve display



High sensitivity and good stability



*Battery level display



Automatic conversion to standard value at 20°C



SF6 Intelligent Micro-Water Dew Point Meter



Technical Parameters



Response time: ≤1min for dew point from +20°C to -20°C;



≤3min for -20°C to -40°C;



≤8min for -40°C to -60°C;



Power supply: 220V AC/DC dual use, one charge lasts 8 hours



Operating environment: Temperature: -20°C to +60°C



Relative humidity: 0 to 95%



Pressure: ≤1.0MPa



Dimensions and weight: 300×220×130mm; 4kg



Field Testing



Operating Steps



First, turn on the power and allow the instrument to perform automatic calibration for about five minutes;



Connect one end of the inlet pipe to the instrument and close the flow control valve; then connect the other end to the equipment under test;



Open the flow control valve and adjust to about 0.6-0.7L/min;



The measurement will be completed automatically within a few minutes (the first sample takes about ten minutes, subsequent continuous measurements usually take only 2-5 minutes; if conversion is needed, refer to the data conversion section). Press the storage key to save data, and repeatedly press the display key to view historical data;



For continuous measurements, do not turn off the instrument power; simply repeat the above steps to save measurement time;



After use, always turn off the power to protect the instrument battery;



Data Conversion



When the ambient temperature is above 20°C and the measured value is higher than the standard value (the allowable moisture content for SF6 equipment at 20°C as specified by national standards), the measured value needs to be converted to the value at 20°C. The method is as follows:



When the measured gas temperature is stable, set the K value to +0.5 in the measurement parameter menu under the settings menu, and the measured value will be the value at 20°C.



When the measured gas temperature is unstable, wait until the measured value stabilizes, then set the K value to +0.5; the displayed value will then be the value at 20°C.



When the ambient temperature is below 20°C, or when the measured value is below the standard value even if the ambient temperature is above 20°C, conversion is generally not needed; in this case, the K value should be 0.


WeChat QR Code
💬
💬 Message ✕

Hello! Have you found what you need? Contact us directly online!

Leave a Message for Consultation
Yangzhou Darui Electric Co., Ltd.
主营产品:Dielectric Loss Tester、Transformer Ratio测试仪、Loop Resistance Tester、高压None线核相仪、Insulation Resistance Tester、Partial Discharge Tester、Cable Fault Tester、DC Resistance Tester等。
☎ Phone: 18952707000(关经理)📞 Landline: 0514-88770377✉ Email: 195214804@qq.com
Verification Code
By submitting, you agree to ourTerms of ServiceandPrivacy Policy
🏠 网站Home📞 一键拨号✉ Contact Us