Detailed Introduction
Equipment Introduction
The TPYBL-SC handheld three-phase zinc oxide arrester tester is a new type of instrument used to detect the electrical performance of zinc oxide arresters. It is suitable for live or outage detection of zinc oxide arresters at various voltage levels, thereby timely discovering dangerous defects such as internal insulation moisture and valve plate aging.
The TPYBL-SC handheld three-phase zinc oxide arrester tester is simple to operate and convenient to use. The entire measurement process is controlled by a microcontroller. It can measure the total current, resistive current and its harmonics, power frequency reference voltage and its harmonics, active power, and phase difference of zinc oxide arresters. The large screen can display the real waveforms of voltage and current. The instrument uses digital waveform analysis technology, automatic frequency conversion technology, harmonic analysis, digital filtering, and other software anti-interference methods to make measurement results accurate and stable. It can accurately analyze the content of the fundamental wave and 3rd to 7th harmonics, and can overcome the influence of inter-phase interference, correctly measuring the resistive current of side-phase arresters. This device is equipped with a rechargeable battery, making it very convenient for field use. The instrument uses a unique high-speed magnetic isolation digital sensor to directly collect input voltage and current signals, ensuring data reliability and safety.
Functional Features
1. This handheld zinc oxide arrester live tester adopts a large-screen LCD display with full Chinese menu operation, making it easy to use.
2. High-precision sampling and processing circuits, advanced Fourier harmonic analysis technology, ensuring more reliable data.
3. This instrument uses a unique high-speed magnetic isolation digital sensor to directly collect input voltage and current signals, ensuring data reliability and safety.
4. This instrument has functions such as resistive current fundamental peak output and side-phase correction.
5. This instrument is equipped with a rechargeable battery, calendar clock, and can store 120 sets of measurement data.
Technical Specifications
1. Total current measurement range: 0~10mA RMS Accuracy: ±(reading×5%+5μA)
2. Resistive current fundamental measurement accuracy (wired without inter-phase interference): ±(reading×5%+5μA)
3. Current harmonic measurement accuracy: ±(reading×10%+10μA)
4. Current channel input resistance: ≤2Ω
5. Reference voltage input range: 25V~250V RMS Accuracy: ±(reading×5%+0.5V)
6. Voltage harmonic measurement accuracy: ±(reading×10%)
7. Reference voltage channel input resistance: ≥1800kΩ
8. AC charging: AC 220V±10%, 50Hz±1%
9. Battery continuous working time: more than 8 hours
10. Battery charging time: more than 6 hours