DC high voltage generator, high voltage generator, DC high voltage generator, medium frequency DC high voltage generator, DC high voltage generating device, DC generator, high voltage DC generator, portable DC high voltage generator, medium frequency DC high voltage generator, high frequency DC high voltage generator, AC/DC high voltage generator, intelligent DC high voltage generator, intelligent DC high voltage generator, intelligent DC high voltage generating device
III. Product Features:
◎ Low ripple coefficient, stable and reliable voltage output, no noise, good reliability
◎ Overvoltage, overcurrent, zero-voltage start and fault protection functions, voltage protection value can be set, display is intuitive
◎ Voltage and current are displayed by LCD, and readings are available as soon as power is on, convenient to monitor output status
◎ With 0.75 times voltage conversion, one-key measurement for zinc oxide arrester and oil-immersed transformer
◎ With withstand voltage timing, ground alarm, calendar, time and printing functions.
◎ Compact structure, small size, easy to carry
IV. Product Parameters:
| Specification Technical Parameters | JGZF-ZN 60KV/2mA | JGZF-ZN 60KV/3mA | JGZF-ZN 120KV/2mA | JGZF-ZN 120KV/3mA |
| Output Voltage (kV) | 60 | 60 | 120 | 120 |
| Output Current (mA) | 2 | 3 | 2 | 3 |
| Output Power (W) | 120 | 180 | 240 | 360 |
| Charging Current (mA) | 2 | 3 | 2 | 3 |
| Control Box Weight (kg) | 2 | 2 | 2 | 2 |
| Voltage Doubler Tube Weight (kg) | 2.5 | 2.5 | 4 | 4 |
| Voltage Doubler Tube Specification (mm) | Ф90 340 | Ф90 340 | Ф90 470 | Ф90 470 |
| Voltage Measurement Error | 0.2% (full scale) ±1 digit | |||
| Current Measurement Error | 0.2% (full scale) ±1 digit | |||
| Overvoltage Setting Error | AI technology sets overvoltage protection and overcurrent protection. Error ≤0.2% | |||
| Intelligent (AI) Test | AI fully automatic zinc oxide arrester and oil-immersed or transformer measurement function. Can directly print test reports and save test reports. Accuracy ≤0.2% | |||
| 0.75 Switching Error | High precision 0.75UDC-1mA single touch button (accuracy ≤1.0%) Suitable for zinc oxide arrester test | |||
| Ripple Coefficient | ≤0.2% | |||
| Working Mode | Intermittent use: rated load for 30 minutes 1.1 times rated voltage use: 10 minutes | |||
| Working Environment | Temperature: -10~40℃ | |||
| Relative humidity: not greater than 85% at room temperature 25℃ (no condensation) | ||||
| Altitude: below 1500 meters | ||||
| With Capacitive Load | No limit on capacitance of test object | |||
| Structural Features | Air insulated, no leakage concerns | |||