Starting and Braking Control of Asynchronous Motors with Relays and Contactors

Traditional squirrel-cage asynchronous motor starting and braking control methods generally include four types: stator circuit series resistance starting, Y/△ starting, autotransformer starting, and extended delta starting; there are three braking methods: reverse braking, dynamic braking, and capacitor braking. The implementation of any of these starting and braking control methods is usually completed by a relay-contactor control system. The following takes stator circuit series resistance reduced-voltage starting and reverse braking as examples to analyze the starting and braking control of squirrel-cage asynchronous motors implemented by relays and contactors.

This control circuit contains three contactors and one intermediate relay coil, with 12 contacts. During starting, both KM2 and KM3 coils are in the disconnected state. Press the start button SB1, the KM1 coil is energized and self-locked, and the motor starts with series resistance reduced voltage. When the motor speed rises to a certain value, the normally open contact of speed relay KS1 closes, the intermediate relay KA is energized and self-locked, the normally open contact of KA connects the contactor coil KM3, and the main contacts of KM3 short-circuit the stator resistance R in the main circuit. When the motor speed rises to the given value, it enters stable operation.

        During braking, press the stop button SB2, the KM1 coil is de-energized, and its main contacts disconnect the three-phase power supply; in the control circuit, the normally open contacts are disconnected, KM3 loses power, and the current-limiting resistor is connected in series; the normally closed contacts close, connecting the reverse braking contactor KM2, swapping the phase sequence of the two-phase power supply, and the motor is in the reverse braking state. When the speed drops to a certain value, the normally open contact of KS1 disconnects KA, then disconnects KM2, the motor loses power, and stops quickly. The capacitor tester uses a new type of excitation coil for non-disassembly measurement of vacuum degree. It has the advantages of convenient use, non-disassembly measurement, and high testing accuracy. It is a practical detection instrument suitable for electric power, steel, petrochemical, textile, coal, railway, and other departments.
        This traditional relay-contactor control method has clear control logic and adopts a combination of mechanical and electrical integration, which is convenient for ordinary mechanical or electrical technicians to maintain. However, due to the large size of electrical components, many contacts, and high failure rate, the reliability of operation is relatively low. With the development of PLC technology, using PLC for motor operation control has become an inevitable trend.


Remarks:

Comparison of PLC and relay-contactor control systems

By comparing the traditional control method and PLC control method for starting and braking of squirrel-cage asynchronous motors, in a sense, PLC control is developed from relay-contactor control. The two have both similarities and many differences.



1. Differences between the two schemes

(1) Most of the interior of PLC uses "soft" logic

Relay-contactor control uses all hardware devices, hard contacts, and "hard" wire connections, which is full hardware control; PLC internally mostly uses "soft" electrical appliances, "soft" contacts, and "soft" wire connections, which is software control;

(2) PLC control system has a compact structure

Relay-contactor control systems use many electrical appliances, are large in size, and have a high failure rate; PLC control systems have a compact structure, use fewer electrical appliances, and are small in size;

(3) All internal "soft contacts" of PLC act quickly

Electrical contactor control uses all mechanical contacts, which act slowly and have severe arc discharge; PLC internally uses all "soft contacts" that act quickly;

(4) Changing PLC control functions is extremely convenient

Changing relay-contactor control functions requires disassembling wires, reconnecting, and even replacing components, which is troublesome; changing PLC control functions generally only requires modifying the program, which is extremely convenient;

(5) PLC control system has a short manufacturing cycle

Due to its simple and compact structure, basically software control, the design, construction, and debugging of PLC control systems take a shorter cycle than relay-contactor control systems.

In addition, since PLC technology is developed on the basis of computer control, its software and hardware settings have advantages that traditional relay-contactor control cannot match, and its working reliability is extremely high.

2. Design points of the PLC scheme

(1) Set up filtering

In PLC, π-type filters are generally set at the input and output interfaces. They can not only filter out high-frequency interference from the outside but also reduce mutual interference between internal module signals;

(2) Provide isolation

In PLC systems, almost all CPUs and I/O circuits (mainly digital ports) are equipped with optocouplers for isolation to prevent interference or possible damage to the CPU, etc.;

(3) Set up shielding

There are two types of shielding: one is to adopt double shielding of magnetic field and electric field for the transformer, in which case materials that are both magnetically conductive and electrically conductive are used as the shielding layer; the other is to only shield modules such as CPU and programmer against electromagnetic fields, in which case conductive metal materials can be used as the shielding layer;

(4) Adopt modular structure

PLC usually adopts a building-block structure, which is convenient for users to repair and replace templates. At the same time, each template is equipped with a fault detection circuit and uses corresponding indicators to mark its status, enabling users to quickly determine the location of the fault;

(5) Provide interlock function

Interlock functions are provided between the output channels in PLC to prevent accidents that may be caused by misoperation between controlled objects;

(6) Set up environment detection and diagnostic circuits

This part of the circuit is responsible for detecting the operating environment of the PLC (such as grid voltage, working temperature, environmental humidity, etc.), and also completes monitoring of the working status of each module in the PLC. This part of the circuit often works in coordination with software to achieve automatic fault diagnosis and prediction;

(7) Set up Watchdog circuit

This kind of circuit in PLC is specifically for monitoring whether the PLC operation process proceeds according to the predetermined sequence. If a fault occurs in the PLC or the user program area is damaged, an alarm is issued because the CPU cannot work according to the predetermined sequence (predetermined time interval);

(8) PLC input and output control is simple

PLC works in a scanning manner, that is, the input of signals, processing of data, and output of control signals are carried out in batch processing at different time intervals within one scan cycle. This not only makes user programming simple and less error-prone, but also makes the PLC's work less susceptible to external interference; at the same time, the data processed by PLC is relatively stable, thereby reducing errors in processing; in addition, the input and output control of PLC is relatively simple, and it is not easy to cause problems due to inappropriate timing.