Matching Usage Method of Insulating Boots Withstand Voltage Device

  1. Before use, first fill water into the water resistor (the water resistor is empty when leaving the factory; do not fill it too full, just submerge the electrode). Install the water-filled water resistor on the mobile bracket, then insert both ends of the electrode rod support into the insulating support rod and the water resistor.

      2. Fill the water tank with water (two-thirds of the entire tank), fill the test object with water, and make the water level inside and outside the insulating boots (gloves) the same height, with a 90mm portion exposed above the water surface. Ensure the exposed part of the insulating boots (gloves) is dry and clean, then place the high-voltage electrode inside the insulating boots (gloves) and properly clamp the
Insulating Boots and Gloves Withstand Voltage Test Device.

     3. Connect the grounding terminal on the insulating boots (gloves) test cart to the ground grid, and also connect the grounding terminal on the insulating boots (gloves) operation box panel to the ground grid, ensuring it is at the same grounding point as the test cart's grounding terminal.

     4. Check whether the main power supply matches the input power (~220V 50Hz), and use the two cables provided with the operation box to connect the operation box to the test bench.

     5.
Control Box Operation Guide

 


Test Item
Item
Cycle
Voltage Level
Requirement
Description
Insulating Boots
Power Frequency Withstand Voltage Test
Half a Year
Voltage Level
Requirement
Description
Insulating Gloves
Power Frequency Withstand Voltage Test
Half a Year
Voltage Level
Requirement
Description