HDKY-CFSeriesBattery Banks



Product Overview;

HDKY-CF
SeriesBattery Bank Online Charge/Discharge Tester integrates online discharge, online charging, whole-group activation, and monitoring functions into one unit.



Features;



Product Features:


●   Online constant current discharge function for batteries, with continuously adjustable discharge current.

●   Online intelligent charging function for batteries, meeting battery charging maintenance requirements.

●   Online monitoring and rapid capacity analysis functions. Real-time online monitoring displays all test data: current, voltage, discharge time, capacity, etc.

●  Whole-group activation function: can set the number of charge/discharge cycles for the entire battery bank, achieving online activation effect.

●  Individual cell monitoring function: cell voltage range 1-20V, supporting 2V, 6V, 12V cell monitoring.

●  Full deep discharge function: supports ten-hour continuous discharge testing, accurately measures battery capacity, and automatically records test data.

●  Automatic shutdown function: automatically stops discharge/charge when any set threshold is reached, such as time limit, capacity limit, battery protection voltage, etc.

●  Protection function: automatically stops protection in case of abnormal voltage, etc.

●  On-site calibration function for voltage and current.

●  Data storage function: automatically collects and saves charge/discharge data. After testing, data can be exported via USB drive to PC for analysis with dedicated software.

●  Backend PC analysis software with multiple analysis functions, capable of generating various test reports, providing basis for judging battery quality.

●   5.7-inch large touch screen: uses a large touch screen, allowing direct touch operation on the screen, making operation simpler and clearer.

     During discharge, all discharge parameters can be viewed, and a bar chart of individual cell voltages can be displayed.



Technical Parameters;





Model HDKY-CF48150 HDKY-CF48300 HDKY-CF22060 HDKY-CF60060 HDKY-CF600100
Bank Voltage 18-60V 18-60V 170-270V 190-600V 190-600V
Discharge Current (Continuously Adjustable) 0-150A 0-300A 110V:0-30A
220V:0-60A
0-60A 0-100A
Charge Current (Continuously Adjustable) 0-150A 0-300A 110V:0-30A
220V:0-60A
0-60A 0-100A
Control Accuracy Discharge current ≤±0.5%; Bank voltage ≤±0.5%; Cell voltage: ≤±0.3%
Weight 11kg 18kg 18kg 23kg 38kg